Control Systems - Study Mode

[#181] Which one of the following compensation is adopted for improving transient response of a negative unity feedback system?
Correct Answer

(A) Phase lead compensation

[#182] A liquid level controller linearly converts a displacement of 2 m to 3 m into 4-20 mA control signal. A relay serves as two position controller to open and close an inlet valve. Relay closes at 12 mA and opens at 10 mA. The hysteresis zone is:
Correct Answer

(B) 0.125 m

[#183] Given the system transfer function $$Gleft( s
ight) = frac{{K{e^{ - 0.2s}}}}{{sleft( {s + 2}
ight)left( {s + 8}
ight)}},$$ xa0 xa0 the corner frequencies in rad/s are
Correct Answer

(D) 2, 8

[#184] A second order LTI system is described by the following state equations [frac{{
m{d}}}{{{
m{dt}}}}] x 1 (t) - x 2 (t) = 0 [frac{{
m{d}}}{{{
m{dt}}}}] x 2 (t) + 2x 1 (t) + 3x 2 (t) = r(t)
where x 1 (t) and x 2 (t) are the two state variables and r(t) denotes the input. The output c(t) = x 1 (t). The system is
Correct Answer

(D) overdamped

[#185] Where are the K = ±∞ points on the root loci of the characteristic equation of the closed loop control system located at?
Correct Answer

(B) Zeroes of G(s)H(s)